Experimentally Validated Effects of Separation of Liquid and Vapor on Performance of Condenser and System

2017-01-0162

3/28/2017

Authors
Abstract
Content
This paper presents the results of an experimental study to determine the effect of vapor-liquid refrigerant separation in a microchannel condenser of a MAC system. R134a is used as the working fluid. A condenser with separation and a baseline condenser identical on the air side have been tested to evaluate the difference in the performance due to separation. Two categories of experiments have been conducted: the heat exchanger-level test and the system-level test. In the heat exchanger-level test it is found that the separation condenser condenses from 1.6% to 7.4% more mass flow than the baseline at the same inlet and outlet temperature (enthalpy); the separation condenser condenses the same mass flow to a lower temperature than the baseline condenser does. In the system-level test, COP is compared under the same superheat, subcooling and refrigerating capacity. Separation condenser shows up to 6.6% a higher COP than the baseline condenser.
Meta TagsDetails
Citation
Li, J., Feng, L., and Hrnjak, P., "Experimentally Validated Effects of Separation of Liquid and Vapor on Performance of Condenser and System," WCX™ 17: SAE World Congress Experience, Detroit, Michigan, United States, April 4, 2017, .